%0 Journal Article %A Silva Quiñonez, Rolando Arturo %T Optimal control for on-load tap-changers and inverters in photovoltaic plants applying teaching learning based optimization %D 2026 %U http://hdl.handle.net/10498/40573 %X The increasing penetration of photovoltaic (PV) generation into modern power systems requires advanced supervisory control strategies capable of ensuring voltage stability, efficient reactive power management, and reliable grid integration. Conventional Energy Management Systems (EMS) and inverter control strategies often neglect the coordinated operation of On-Load Tap-Changers (OLTCs), mechanical aging effects, and inverter operating constraints, resulting in suboptimal performance under dynamic operating conditions. This doctoral research develops and experimentally validates an optimized EMS based on an enhanced Teaching–Learning-Based Optimization (TLBO) algorithm for the coordinated real-time control of PV inverters and OLTC transformers. The proposed framework integrates electrical, mechanical, and economic objectives within a unified optimization process to improve voltage regulation, reactive power support, and equipment lifetime while minimizing operating costs. A high-fidelity model of a dual 100 kWp photovoltaic installation coupled to a 300 kVA OLTC transformer was developed in MATLAB/Simulink. The EMS simultaneously optimizes inverter active and reactive power references together with OLTC tap positions while considering PQ capability curves, voltage deadband, mechanical latency, switching costs, and thermal constraints. The proposed optimized TLBO incorporates adaptive learning mechanisms, feasibility correction, and early stopping criteria to accelerate convergence while guaranteeing feasible operating solutions. Its performance was benchmarked against Monte Carlo, nonlinear fmincon, and conventional TLBO algorithms. Simulation results demonstrate that the proposed algorithm converges within 3–6 ms, compared with approximately 0.3–0.4 s for conventional optimization methods, while maintaining 100% feasibility under all operating constraints. The optimized TLBO reduces the objective function by 17–25% relative to the conventional TLBO, limits OLTC operations to fewer than 20 tap changes per day, improves reactive power sharing between PV units, and enhances voltage regulation at the point of common coupling. Hardware-in-the-Loop validation using OPAL-RT, dSPACE MicroLabBox, and Yokogawa instrumentation confirmed the real-time applicability of the proposed EMS, with measurement deviations below 2% and implementation costs below 0.1% of plant CAPEX. The proposed methodology contributes a novel supervisory control architecture integrating adaptive TLBO optimization with coordinated OLTC–inverter operation. The results demonstrate improved operational efficiency, reduced mechanical stress, enhanced grid support capability, and a scalable solution suitable for future hybrid renewable energy systems. %~ Universidad de Cádiz