Experimental adjustment of the turbulent Schmidt number to model the evaporation rate of swimming pools in CFD programmes

Identificadores
URI: http://hdl.handle.net/10498/27882
DOI: 10.1016/j.csite.2022.102665
ISSN: 2214-157X
Statistics
Metrics and citations
Share
Metadata
Show full item recordDate
2023-01Department
Física Aplicada; Máquinas y Motores TérmicosSource
Case Studies in Thermal Engineering, Vol. 41Abstract
Water evaporation rate is among the most significant parameters to design and select air con-ditioning systems in buildings with indoor swimming pools. Experimental correlations are today widely used to estimate water evaporation rate, although discrepancies of up to 80% among existing correlations have been shown. An alternative to these empirical methods is the calcu-lation of evaporation rate through computer fluid dynamics techniques. One of the most signif-icant parameters to solve the mass transfer at the air-water interface in these models is the value of the turbulent Schmidt number. Although this value depends on air and water conditions (i.e., temperatures, velocities, and vapour pressure, among others), commercial computer fluid dy-namics programmes set a fixed value by default. This study presents a new value through an experimental adjustment. A total of 40 experimental tests have been performed in a wind tunnel under typical conditions in indoor swimming pools. Afterwards, the adjustment was validated with data from 145 experimental tests reported in the scientific literature. The mean relative error in the evaporation rate using the turbulent Schmidt number was 7%, as against 25% using the value by default. The maximum error was reduced from 35% to 15% in forced convection regime.