dc.description.abstractThis paper proposes an easy-to-implement method for detecting and assessing two of the most frequent PQ (Power Quality) problems: voltage sags and swells. These can affect sensitive equipment such as computers, programmable logic controllers, contactors, etc. Therefore, it is of great interest to implement it in any laboratory, not only for protection reasons but also as a safeguard for claims against the supply company. Thanks to the actual context, in which it is possible to manage big volumes of data, connect multiple devices with IoT (Internet of Things), etc., it is feasible and of great interest to monitor the voltage at specific points of the network. This makes it possible to detect voltage sags and swells and diagnose which points are more prone to this type of problems. For the detection of sags and swells, a program written in Python is in charge of crawling all the files in the database and target those RMS values that fall outside the established limits. Compared to LabVIEW, which might have been the most logical alternative, being the acquisition hardware from the same company (National Instruments), Python has a higher computational performance and is also free of charge, unlike LabVIEW. Thanks to the libraries available in Python, it allows a hardware control close to what is possible using LabVIEW. Implemented in MATLAB, the ITIC (Information Technology Industry Council) power acceptability curve reflects the impact of these power quality disturbances in electrical power systems. The results showed that the combined action of Python and MATLAB performed well on a conventional desktop computer.es_ES
dc.formatapplication/pdfes_ES
dc.language.isoenges_ES
dc.publisherMDPIes_ES
dc.rightsAtribución 4.0 Internacional*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/*
dc.sourceData. Vol. 7, nº 11, November 2022, 162es_ES
dc.subjectAcceptance curvees_ES
dc.subjectHigh order statisticses_ES
dc.subjectInformation technology industry council (ITIC)es_ES
dc.subjectObservational dataes_ES
dc.subjectQuality indiceses_ES
dc.subjectVoltage sagses_ES
dc.subjectVoltage swellses_ES
dc.titleMethodology for the Surveillance the Voltage Supply in Public Buildings Using the ITIC Curve and Python Programminges_ES
dc.typejournal articlees_ES
dc.rights.accessRightsopen accesses_ES
dc.description.physDesc10 páginases_ES
dc.identifier.doi10.3390/data7110162
dc.relation.projectIDinfo:eu-repo/grantAgreement/AEI/Plan Estatal de Investigación Científica y Técnica y de Innovación 2017-2020/PID2019-108953RB-C21/ES/DATOS OPERACIONALES ENERGETICOS Y METEOROLOGICOS PARA SISTEMAS FOTOVOLTAICOS/es_ES
dc.relation.projectIDinfo:eu-repo/grantAgreement/Junta de Andalucía//FEDER-UCA18-108516es_ES