Show simple item record

dc.contributor.authorCarrasco González, David 
dc.contributor.authorHorrillo Quintero, Pablo 
dc.contributor.authorGarcía-Triviño, Pablo
dc.contributor.authorSarrias Mena, Raúl 
dc.contributor.authorGarcía Vázquez, Carlos Andrés 
dc.contributor.authorFernández Ramírez, Luis Miguel 
dc.contributor.otherIngeniería Eléctricaes_ES
dc.contributor.otherIngeniería en Automática, Electrónica, Arquitectura y Redes de Computadoreses_ES
dc.date.accessioned2024-06-26T13:57:23Z
dc.date.available2024-06-26T13:57:23Z
dc.date.issued2024
dc.identifier.issn0142-0615
dc.identifier.urihttp://hdl.handle.net/10498/32783
dc.description.abstractAt the present time, quasi-Z-source cascaded H-bridge multilevel inverters (qZS-CHBMLI) have gained attention in photovoltaic (PV) applications, due to their advantages over traditional multilevel inverters. They allow single-stage power conversion of a PV power plant by independently adjusting the DC voltage in each module; thus, each PV array operates at the maximum power. This advantage permits dispensing with a DC/DC boost converter and reduces the number of modules required. This paper develops a novel control strategy for a qZS-CHBMLI connected to a single-phase system that guarantees proper operation when a fault occurs in a quasi-impedance source inverter (qZSI). The control strategy is employed in a grid-connected qZS-CHBMLI with three modules, each one with a quasi-impedance network, a 4.8 kW PV array and a voltage source inverter (VSI), with H-bridge topology. The purpose of the control system is to deliver a suitable DC voltage at the input of the VSI and ensure the grid power requirements after a fault in a module. The proposed control system is evaluated through a 40 s simulation in MATLAB/Simulink® in two cases: A) analysis of the system behaviour when there is a variation in the operation limit equation; and B) evaluation of the control strategy under dissimilar operating conditions. In addition, an experimental setup based on an OPAL RT-4510 unit and a dSPACE MicroLabBox prototyping unit is employed to validate the results. The results confirmed the correct response of the applied strategy with the failure of a single module.es_ES
dc.formatapplication/pdfes_ES
dc.language.isoenges_ES
dc.publisherElsevieres_ES
dc.rightsAtribución 4.0 Internacional*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/*
dc.sourceInternational Journal of Electrical Power and Energy Systems, Vol. 157, 2024es_ES
dc.subjectControl systemes_ES
dc.subjectPhotovoltaic power plantses_ES
dc.subjectQuasi-Z-source cascaded H-bridge multi-level inverteres_ES
dc.titleControl of PV power plants with quasi-Z-source cascaded H-bridge multilevel inverters under failurees_ES
dc.typejournal articlees_ES
dc.rights.accessRightsopen accesses_ES
dc.identifier.doi10.1016/J.IJEPES.2024.109803
dc.relation.projectIDinfo:eu-repo/grantAgreement/Junta de Andalucia//PY20_00317es_ES