RT journal article T1 Dynamic evaluation of two configurations for a hybrid DFIG-based wind turbine integrating battery energy storage system A1 Sarrias Mena, Raúl A1 Fernández Ramírez, Luis Miguel A1 García Vázquez, Carlos Andrés A1 Jurado, Francisco A2 Ingeniería Eléctrica A2 Ingeniería en AutomáticaElectrónica, Arquitectura y Redes de Computadores K1 doubly fed induction generator K1 energy storage system K1 Hybrid system K1 wind energy AB Hybrid systems comprising battery energy storage systems (BESSs) and wind power generation entail considerable advances on the grid integration of renewable energy. Doubly fed induction generators (DFIGs) stand out among differentwind turbine (WT) technologies. On the other hand, electrochemical batteries have proved to be valid for these purposes.In this paper, a comparative analysis is carried out between two alternative configurations for hybrid WT-BESS systems,where the BESS is connected either outside or inside the DFIG. The modeling of these two configurations and the controlsystems applied for achieving the coordinate operation of the energy sources (DFIG and batteries) are illustrated. The hybridsystems under study are evaluated by simulation under normal operation (wind speed fluctuations and grid demand changes)and grid faults. Simulation results show that both configurations improve the grid integration capability of the WT, althoughthe configuration with external BESS presents better results since it can provide additional active/reactive power injection. PB John Wiley & Sons. SN 1095-4244 YR 2014 FD 2014-06-11 LK http://hdl.handle.net/10498/34581 UL http://hdl.handle.net/10498/34581 LA eng DS Repositorio Institucional de la Universidad de Cádiz RD 10-may-2026