Evaluating the inertia of the Jordanian power grid

Identificadores
URI: http://hdl.handle.net/10498/29425
DOI: 10.1016/j.compeleceng.2023.108748
ISSN: 0045-7906
Ficheros
Estadísticas
Métricas y Citas
Metadatos
Mostrar el registro completo del ítemFecha
2023-05-26Departamento/s
Ingeniería Eléctrica; Ingeniería en Automática, Electrónica, Arquitectura y Redes de ComputadoresFuente
Computers and Electrical Engineering.Vol. 109, August 2023, 108748Resumen
The increasing penetration of renewable energy sources in power grids has resulted in the need for a comprehensive evaluation of their impact on the dynamic behavior of the power system, including its inertia. This study aimed to evaluate the inertia of the current Jordanian power system at different penetration levels of renewable energy sources using DIgSILENT PowerFactory simulation software. In this study, the value of the constant inertia was calculated to be 8.755 s. The results were analyzed to determine the effect of renewable energy penetration on the inertia of the power system. The findings provide valuable information for the development of control strategies for integrating renewable energy sources into the Jordanian power system, ensuring stability and reliability in the power system operation. This study contributes to the understanding of the impact of renewable energy sources on power system inertia and supports the development of renewable energy integration strategies.