Improving frequency characterization for power systems using the Allan variance and a GPS-controlled reference: Measurement procedure, test and validation

Thumbnail
Identificadores

URI: http://hdl.handle.net/10498/34353

DOI: 10.1016/j.measurement.2022.111395

ISSN: 0263-2241

Ficheros
version aceptada, no maquetada por el editor (4.035Mb)
Estadísticas
Ver estadísticas
Métricas y Citas
 
Compartir
Exportar a
Exportar a MendeleyRefworksEndNoteBibTexRIS
Metadatos
Mostrar el registro completo del ítem
Autor/es
González de la Rosa, Juan JoséAutoridad UCA; Sierra Fernández, José MaríaAutoridad UCA; Florencias Oliveros, OliviaAutoridad UCA; Espinosa Gavira, Manuel JesúsAutoridad UCA; Palomares Salas, José CarlosAutoridad UCA; Agüera Pérez, AgustínAutoridad UCA
Fecha
2022-06-03
Departamento/s
Ingeniería en Automática, Electrónica, Arquitectura y Redes de Computadores
Fuente
Measurement Volume 198, July 2022, 111395
Resumen
La interconexión de las redes inteligentes modernas ha dado lugar a varias nuevas perturbaciones de la calidad de la energía (PQ) que afectan a los requisitos de estabilidad de frecuencia en los sistemas eléctricos industriales. La frecuencia, que oscila entre 50 ± 0,1 Hz para las redes interconectadas e incluso dentro del área síncrona europea, fluctúa principalmente debido al control primario. De hecho, debido al desarrollo de recursos distribuidos (por ejemplo, energías renovables), no todas las unidades de generación son accesibles y solo son controlables en unos pocos nodos de la red. Esta variabilidad, incluso entre ubicaciones cercanas, desencadena la necesidad de estrategias de medición específicas, basadas en una referencia absoluta y también concebidas para monitorear las perturbaciones de PQ. Este trabajo propone un método sincronizado con GPS, fácil de implementar, que permite la medición de frecuencia con una precisión mejor que la requerida por la regulación actual para redes interconectadas. Este trabajo explica la metodología de medición, caracterizando la incertidumbre mediante el uso de la norma ISO JCGM 100. Con el propósito de probar y validar, se llevaron a cabo tres experimentos: perturbaciones de laboratorio diseñadas por computadora y activadas por instrumentos, y una comparación con el desempeño de PMU, utilizando señales de la vida real. Los resultados mostraron que estos experimentos ofrecieron un mejor desempeño con una incertidumbre mejorada.
 
The interconnected modern smart grid has resulted in several new power quality (PQ) disturbances that affect the frequency stability requirements in industrial power systems. Ranging between 50 +-0.1 Hz for interconnected networks, and even within the European synchronous area, the frequency fluctuates mainly because of the primary control. In fact, owing to the development of distributed resources (e.g. renewable energies), not all generation units are accessible, and are controllable in a few network nodes. This variability, even between nearby locations, triggers the need for a specific measurement strategies, based on an absolute reference and also conceived for monitoring PQ disturbances. This work proposes an easy-to-implement GPS-traceable method that allows the measurement of frequency with better accuracy than that required by the current regulation for interconnected networks. This work explains the measurement methodology, characterising the uncertainty by using ISO JCGM 100. For the purpose of testing and validation, three experiments were conducted: computer-designed, instrument-triggered lab disturbances, and a comparison vs. PMU performance, using real-life signals. The results showed that these experiments offered better performance with improved uncertainty
 
Materias
Frequency stability; GPS-PPS reference; Synchronous acquisition; Power Quality; Power Systems Characterisation; Uncertainty calculation
Colecciones
  • Artículos Científicos [12009]
  • Articulos Científicos Ing. Sis. Aut. [193]
  • Artículos Científicos IVAGRO [733]
Attribution-NonCommercial-NoDerivatives 4.0 Internacional
Esta obra está bajo una Licencia Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 Internacional

Listar

Todo RODINComunidades y ColeccionesPor fecha de publicaciónAutoresTítulosMateriasEsta colecciónPor fecha de publicaciónAutoresTítulosMaterias

Mi cuenta

AccederRegistro

Estadísticas

Ver Estadísticas de uso

Información adicional

Acerca de...Deposita en RODINPolíticasNormativasDerechos de autorEnlaces de interésEstadísticasNovedadesPreguntas frecuentes

RODIN está accesible a través de

OpenAIREOAIsterRecolectaHispanaEuropeanaBaseDARTOATDGoogle Académico

Enlaces de interés

Sherpa/RomeoDulcineaROAROpenDOARCreative CommonsORCID

RODIN está gestionado por el Área de Biblioteca, Archivo y Publicaciones de la Universidad de Cádiz

ContactoSugerenciasAtención al Usuario